SYSTEM DESCRIPTION
Single or multiple cylinder systems are applied depending on the volume of the protected areas. In a Multi-Cylinder System, the Pilot Flask is used to activate the system cylinders. The Pilot Bottle is automatically activated using the detonator which is triggered by the Fire Detection-Extinguishing Panel of the System. The Table receives a command from a Detection System consisting of pairs of Heat Detectors and Smoke Detectors. It is manually activated either by pushing the Shutter Piston or by a Remote Manual Activation Knob. The "Pilot" Cylinder Slide is connected via a High Pressure Flexible EPDM Tube to the 1st cylinder shutter of the system. In essence, when the Pilot Cylinder is activated, the propellant gas activates pneumatically the Shutters of the main System Dioxide Cylinders (the Shutters of the main Bottles of the System are connected by Flexible EPDM High Pressure Pipes). Once the main Flasks of the System are activated, the Extinguishing Material is forwarded through Flexible EPDM High Pressure Pipes to the System Collector from where it is driven to Launchers.
THE SYSTEM INCLUDES
Cylinders Certified Cylinders IG541 16Lt, 40Lt, 50Lt, 67.5Lt and 80Lt with Automatic, Manual or Pneumatic Activation Shutter (with or without Manometer), Protection Disc and Heavy Duty Mounts. • Certified Bottle "Pilot" 3lt (2Kg) with Automatic, Manual or Pneumatic Shutter and Heavy Duty Base. Collector Fittings – Collector Pipe Cross Section from 11/4" to 3" – Tomb Cross Section Collector from 11/4" to 3" – Tapa Collector size from 11/4" to 3" – Intersection Collector Contraction 1/4" = > 3/4", 2" = > 1", 21/2" = > 11/2", 3"= > 2". – 3/4" Non-return Valve. EPDM Hoses • EPDM High Pressure Hosse connection of "Pilot" Bottle to the Shutter of the first Multi-Cylinder Cylinder Cylinder Cylinder Cylinder ( Flexible Tube • EPDM Flexible Tube high pressure cylinder connection of multi-cylinder system • EPDM Flexible Tube high pressure connection of system cylinders with Reverse Valve Collector • EPDM flexible tube high pressure cylinder connection of one cylinder system with ejector network Other Fittings – Breast (3/8" – 3/8") – for the connection Flexible EPDM Tubes in the System Cylinder Shutters – 3/8" Tapa for Output Sealing of the Pilot Cylinder and the last Cylinder of the System – Diameter Launchers from 1/2" to 1 1/2" – Output Pressure Regulator IG -541 (from 200bar to 60bar) Fire detection • Certified Four-zone Table • Optical-Acoustic Siren • Manual System Activation Knob • Extinguishing Knob • Fire Extinguishing Knob • Heat Detectors (Thermal Limit or Thermodhidifiers) • Detectors Tobacco • STOP GAS PLATE TEXNIKES SPECIFICATIONS The Recommendation of IG 541 is: NITROGEN 52% ± 4%, ARGO 40% ± 4%, CARBON DIOXIDE 8% ±4% ISO 9809 – 1 ΕΝ 1964 – 1 p 99/36/ΕC CE VILLAS PILOT 97/23/ΕC (TUV) – CE KLISTRO (BAM) CE 0589